SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 1 OF 9

Specification for

Package Instrument

PROJECT NAME : Liquid Hydrogen Refueling Station Project

CLIENT : SK E&S Plug Power

Contractor : Korea Gas Technology Corporation(KOGAS-Tech)

(Tech. advisor)

LOCATION : South Korea

REV. PREPARED CHECKED APPROVED

DATE DESCRIPTION

NO. BY BY BY

A 2021.10.29 Issued for Quotation W.S.LEE W.J.JANG M.K.KIM

ALL INFORMATION HEREON IS THE CONFIDENTIAL PROPERTY OF KOGAS-TECH SUBJECT TO RETURN ON DEMAND AND MUST NOT BE MADE PUBLIC OR REPRODUCED

WITHOUT WRITTEN APPROVAL

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

TABLE OF CONTENTS

CODE AND STANDARD................................................................................................................................................................. 3

GENERAL REQUIREMENTS .......................................................................................................................................................... 6

DESIGN ................................................................................................................................................................................................. 7

ACCESSORIES ...................................................................................................................................................................................11

INSTALLATION .................................................................................................................................................................................13

PAINTING ...........................................................................................................................................................................................15

NAME PLATES..................................................................................................................................................................................15

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

CODE AND STANDARD

1.1 Relevant Standards and Codes of practice

The latest edition of the following standards and codes should be used. The requirements of

this and any other relevant project specifications take precedent over the requirements of the

listed standards.

ASME B1.20.1 Pipe Threads, General Purpose (Inch)

ASME B16.5 Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24

ASME B16.10 Face-to-Face and End-to-End Dimensions of Valves

ASME B16.34 Valve-Flanged, Thread and Welding End

ASME B46.1 Surface Texture (Surface Roughness, Waviness, and Lay)

ASME PTC19.3 Temperature Measurement

API 550 Manual on Installation of Refinery Instruments and Control

Systems

API 670 Vibration, Axial Position and Bearing Temperature Monitoring

System.

API 678 Accelerometer Based Vibration System.

API RP520 Sizing, Selection, and Installation of Pressure-Relieving Devices

in Refineries

FCI 70.2 Control Valve Seat Leakage

ISA.RB31.1 Specification, Installation & Calibration of Turbine Flow Meters

ISA.S75.01 Flow equations for sizing control valves

ISA.S5.1 Instrumentation in symbols and identification

ISA.S5.2 Primary logic diagrams for process operation

ISA.MC96.1 Temperature Measurement Thermocouples

ISA RP3.2 Flange Mounted, Sharp-Edged Orifice Plates for Flow

Measurement

IEC 60034-1 Rotating Electrical Machines - Rating and performance motor

operated valves

IEC 60073 Basic and Safety Principles for Man-Machine Interface, Marking

and Identification-Coding Principles for Indication Devices and

Actuators

IEC 60079 Electrical apparatus for explosive gas atmosphere

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

IEC 60529 Classification of degrees of protection provided by enclosures

IEC 60584 Thermocouples for temperature measurement

Part 1 : Reference tables

Part 2 : Tolerances

IEC 60654 Operating conditions for industrial-process measurement &

control equipment

IEC 60751 Industrial Platinum Resistance Thermometer Sensors.

IEC 60801 Electromagnetic compatibility for process measurement and

control equipment

IEC 61508 Functional safety of electrical/electronic/programmable

electronic safety related systems

IEC 61511 Functional safety - safety instrumented systems for the process

industry sector

ISO 5167-1 Measurement of fluid flow by means of pressure differential

devices Inserted in circular cross-section conduits running full

ISO 8310 Refrigerated hydrocarbon and non-petroleum based liquefied

gaseous fuels

ISO 17089 Measurement of fluid flow in closed conduits - Ultrasonic meters

for gas

ISO 5167 Measurement of fluid flow by means of pressure differential

devices inserted in circular

ISO 9951 Measurement of gas flow in closed conduits – Turbine meters

NFPA 59A Standard for the Production, Storage, and Handling of Liquefied

Natural Gas (LNG)

NFPA 70 National Electric Codes

NFPA 72 National Fire Alarm Code

NFPA 496 Purged Enclosures for Electrical Equipment

EN 1473 Installation and Equipment for Liquefied Natural Gas – Design

of Onshore Installations

EN 1532 Installation and Equipment for Liquefied Natural Gas – Ship to

Shore Interface

KS C 3341 Halogen free flame retardant poly-olefin power control insulation

wire

KS C 60331-11 Tests for electric cables under fire conditions - Circuit integrity -

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

Part 11: Apparatus - Fire alone at a flame temperature of at least

750 ℃

KS C 60331-21 Tests on Electric Cables under Fire Conditions-Circuit Integrity.

-Part 21 : Procedures and requirements-Cable of rated voltage

up and including 0.6/1.0kV

1.2 It shall be the responsibility of Vendor that all aspects of the design, fabrication, inspection

and testing conform to the requirement of the specified code and standard.

1.3 All applicable Korean local regulations (laws, acts, regulations, etc.) shall be applied, if

applicable. Vendor shall be responsible for determining and complying with the requirements

of all applicable local regulations (laws, acts, regulations, etc.)

1.4 Where there are any conflict between Contractor’s data sheets (drawings) and the specified

codes and standards, such conflicts shall be promptly referred to Contractor.

1.5 Explosion proof type electric equipment & instruments are required to be certified by Korean

Authorities (KOSHA, KTL or KGS) for usage in Korea.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

GENERAL REQUIREMENTS

2.1 Instruments and Materials

2.1.1 The Vendor shall supply the complete set of instruments mounted, piped, wired and

shipped as an integral part of the package, including all instruments, local control panels,

local gauge boards, junction boxes, cables and erection materials necessary for the

operation of the packaged equipment.

2.1.2 The Vendor shall supply instruments specially adapted to the equipment being furnished

by reason of special connections or other special feature not available from instrument

suppliers on the open markets, such as special thermocouples or RTD’s for bearing

temperatures, vibration monitoring heads with parts integral with the equipment.

2.1.3 The Vendor shall supply those instruments that, although mounted remotely from the

packaged equipment, are required for any acceptance or performance testing called for by

the Contractor.

2.1.4 The Vendor shall supply Sunshade for electric instruments, junction boxes, Local Control

Panel(LCP), Local Control Station(LCS), Push Button Box and Local Gauge Board, if

requied.

2.2 Installation, Inspection and Test

2.2.1 Installation, calibration, inspection and testing of the instruments shall be carried out at the

vendor`s shop by the Vendor, including necessary preparation for the execution, unless

otherwise specified in the Requisition.

2.2.2 Acceptance criteria shall be in accordance with the applicable codes and standards or the

vendor’s standard which is approved by the Company.

2.3 Vendor's Drawings, Documents and Data Required

The Vendor shall submit to the Company the drawings and documents as called for in the

Company 's requisition. The Contractor's approval for such drawings and documents shall

not relieve the Vendor of his responsibility to meet all requirements of the purchase order,

applicable codes and standards.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

DESIGN

3.1 Design General

3.1.1 Selection of Instrument

1) Instruments shall be selected for industrial quality, optimum accuracy, and durability. All

instruments, devices and installation materials shall be chosen from the ones, which are

used by up-to-date practice, and shall be suitable for process characteristics of fluids to

be measured, climatic conditions of the plant site, the requirements on electrical area

classification and safe operation.

2) Instrument installation design shall follow the provisions of API RP 551 “Process

Measurement Instrumentation”.

3) Replacements, spare parts, and services shall be readily available for all instruments.

4) The selection of the instruments except those specified shall be determined by the

Vendor in accordance with his good practice and proven experience, but the instruments

the Vendor shall be submitted for the Company`s approval.

Vendor shall select all instrumentation and control systems taking into account site

standardization and to reduce spare parts.

5) Electric signal transmitter shall be supplied smart type with HART protocol for signal

transmission with integral Digital indicators. Transmitter should be smart type with self-

diagnosis.

6) The Vendor shall supply RTD’s(Dual element type) with transmitter(Hot-Backup). RTD’s

sensor element and transmitter shall be supplied separated type.

7) All temperature transmitters which be supplied by package the Vendor shall have

backup function for automatically switches-over from the primary to the backup upon

sensor failure.

8) Surge protection terminals for all input/output signal(5kA), Power(20kV) and

Communication as“Weidmuller, Phoenix contract or equivalent”. Surge Protection

devices shall be provided at the field instrument and at the controller end for the

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

instrument loops. Field instruments shall be provided with transient protectors to prevent

damage from lightning, welding, high voltage, etc.

9) All instruments and systems (including package equipments) shall be supplied with

models which are compatible and interchangeable with each other for maintenance.

3.1.2 Control System Outline

1) The Vendor shall provide all the necessary equipment to perform the control and

monitoring of the packaged equipment.

2) For the control system, PLC shall be used for the control and monitor of the mechanical

package. Packaged equipment which under controlled by its own PLC shall be provided

with dedicated safety logic solver in order to manage any safety related signal.

3) Fail-safe design of instrument and control system shall be considered for safety of

personnel and equipment of the unit under the failure of instrument air and/or electric

power.

4) The PLC shall include redundant CPU, IO module, Communication module, and power

supply for All package items. (System Redundancy : CPU, I/O module, Communication

Module and Power Supply)

5) PLC & HMI

- The Vendor shall supply to the Company the Configuration software, Programming

source, PLC program editing software and HMI(minimum 15” display screen with

intuitive touch screen)

- The Vendor shall provide state of art computer system model with OS of PLC and

HMI and security patch and anti virus program.

- The Vendor shall provide software license key for PLC & HMI System.

3.1.3 Explosion Proof Protection

1) Electrical and electronic instruments, control valves, control equipment (e.g. panels) and

their accessories to be installed in electrical hazardous area shall have suitable

explosion proof constructions.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

2) Type of explosion-protection for the equipment shall normally be chosen from the

following criteria.

- Flame Proof Type (Ex-d, IEC60079-1) : General instruments

- Intrinsically Safe Type (Ex-i, IEC60079-3) : Instruments for which the explosion-proof

type is not applicable and special instruments which are agreed by the Contractor in

advance.

- Purged Type (Ex-p, NFPA 496 , ISA-S12.4 or IEC60079-2) :Local Control Panel, etc.

agreed by the Contractor in advance. The Vendor shall be applied “X”, “Y”, “Z” type

according to hazardous classification.

3) Explosion proof type electric equipment & instruments are required to be certified by

Korean Authorities (KOSHA, KTL or KGS) for usage in Korea.

3.1.4 Electric Power Supply for Instruments

1) The specification for the power shall be as follows.

Voltage and frequency, and their variation shall be as specified on the Data Sheets. The

variation of voltage and frequency will be expected ±10% and ±3% respectively,

unlessotherwise specified on the Data Sheets.

- 220V AC 1ph 60Hz(UPS) : PLC, Instrument, control panels

- 220V AC 1ph 60Hz(Normal): Illumination for local panel

- 24V DC : Alarm unit, Interlock/Shut down circuit, Instrument, SOV

2) The redundant power supply unit(24VDC) for alarm, interlock circuit and field

instruments etc. shall be provided by the Vendor.

3.1.5 Materials

The component parts of the instrument shall be of material suitable for process.

3.2 Control Panel and Gauge Board

The specification of panel(s) to be provided by the Vendor shall be as follows.

3.2.1 Type

1) Control panels mounted in substation or field shall be of free-standing closed type with

hinged doors at the rear or front.

- Unit Control Panel(UCP, including PLC) is located in Substation.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

- Local Control Panel(LCP, including PLC) is located in field.

2) Single door will be acceptable for the panel width 800 mm and below. multiple doors

shall be provided for the panel width over 800 mm. The multiple doors shall be no wider

than 600 mm.

3) Local control panel mounted in field shall be of self-standing and weather proof type (IP

65 or equivalent) with explosion proof, corrosion protection and illuminator, and shall be

of explosion proof type or air purged and pressurized type according to hazardous

classification.

The purge and pressurized panel mounted operators such as push buttons and selector

switches shall be NEMA Type 4 rated or oil-tight and should not contain illumination

devices, unless they are protected.

- Eye bolts shall be provided at top of panels.

- The gauge board may be of open type.

- Material and thickness of Local Control Panel(located in the field) shall be Stainless

steel and front door 3.0t, side and rear 2.0t

3.2.2 Prefabrication

All of the instruments, their components and internal wiring and tubing shall be completely

prefabricated at shop before shipment.

3.2.3 Dimensions

1) Overall dimensions of the panels mounted in control room shall be 800W * 2,100H *

800D(mm) including 100 mm height of channel base(Rittal or equivalent).

Overall dimensions of the local control panels or gauge board shall be in accordance

with Manufacturer's standard, unless otherwise specified in the Requisition.

2) The instruments on the gauge board front shall be fitted between a height of 1 m and 2

m with no part lower and higher.

3.2.4 Color

Finish color of panel inside shall be of manufacturer standard unless otherwise specified.

Finish color of panel external shall be Munsell No. 7.5 BG 6/1.5 and shall be subject to the

Contractor’s approval.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

3.2.5 Wiring and Tubing

1) Internal wiring and tubing in local control panel shall preferably be contained in plastic

ducts for wiring and raceway for tubing routed in an orderly manner to instruments or

apparatus. Wiring and tubing marker shall be installed.

2) Cables for control panel, local panel and junction box shall enter from the bottom.

3.2.6 Instrument Air Supply System

1) Each local pneumatic instrument shall have an individual air set (filter and regulator with

output gauge) with the block valve.

2) Air set (filter and regulator with supply and output gauge) shall be provided for air purge

or pressurizing into local control panel in accordance with NFPA 496 or ISA S.12.4

whenever it is required.

3.2.7 Allocation of Panel

Local control panel or gauge board shall be located at the vibration-free place suitable for

operation and maintenance.

3.2.8 Unit Control Panel and Local Control Panel

When UCP/LCP or Interlock rack/panel is provided for the control and/or protection of

equipment (or packaged system), all alarm and interlocking system shall generally be

provided in the UCP/LCP or Interlock rack/panel.

ACCESSORIES

4.1 All normally-furnished manufacturer's standard accessories for each instrument shall be

provided.

4.2 All field mounted instruments shall be provided with mounting bracket with stainless steel

U-bolt and nuts for 2 inch (50 mm) pipe, unless other installation methods are applied.

4.3 5-way/2-way manifolds shall be provided for the differential pressure instruments/pressure

gauge except for the diaphragm seal type. The rating and material shall meet the process

conditions.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

4.4 Diaphragm seal shall be furnished when required by the process conditions. Capillary tubing

extension length, when required for remote diaphragm seal type pressure or differential

pressure instruments, shall be as short as possible but suitable for installation. And material

of tube and armor shall be stainless steel.

4.5 Air Filter Regulator

4.5.1 An air filter regulator assembly shall be supplied for each pneumatic instrument.

4.5.2 The air filter regulator assembly shall incorporate a filter, a regulator with set screw

adjustment, and a pressure gauge (MPa) to indicate the regulated air pressure.

4.5.3 The air filter regulator assemblies shall be mounted and piped to the instrument at factory.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

INSTALLATION

5.1 Installation of Instruments

As a rule, field-mounted instruments shall be prefabricated in the packaged equipment prior

to shipment, and the pressure piping, air supply piping, signal tubing/wiring etc. shall be also

be installed as far as possible.

5.2 Cable Way and Wiring

5.2.1 Unless otherwise specified in the requisition, the Vendor shall be responsible for the

provision of all cables, cabling materials, ladder rack, trays, lugs, conduits and fittings, cable

glands (certified as appropriate) and all associated accessories which are required to

interconnect items within his supply or battery limits.

5.2.2 Overhead cable tray with protection cover shall be used for main cable way. For protection

of branched cables, conduit pipes shall be used. Cable tray shall be made of hot-dip

galvanized steel plates and/or frames. Cable tray cover shall be made of stainless steel

plates.

5.2.3 Conduit System.

1) Hot dipped galvanized rigid steel conduit and fittings system shall be applied to, all the

wiring in the unit. Closed conduit system shall normally be applied.

2) Flexible conduit connections shall be used to avoid transmission of vibration from

vibrating equipment to the conduit system. It shall also be used to terminate periodically

removable connections such as to instruments, and thermocouples. Maximum length of

flexible conduit connections shall be 1000 mm (40 inches).

3) Conduit bodies and junction boxes shall be accessible from platforms, ladders, and

stairways and shall be supported independent of conduit system. Whenever practical,

horizontal conduits shall be sloped for drainage. Conduit shall not be installed behind

the ladder rungs or at platform levels in such a manner as may cause false and insecure

step. Drain plugs (or breathers) shall be installed at lowest point of vertical conduit runs.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

4) Cable and conduit entrances into enclosures shall be positioned only for bottom or side

entry into enclosures.

5) When the units are divided and consist of two or more sections (or skids), the Vendor

shall provide terminal boxes on each section of the unit for wiring between sections.

6) Flexible conduit and packing type cable gland that were made of stainless steel(316SS)

shall be used flameproof-Ex ‘d’ type

5.2.4 Instrument cable specifications shall be as follows

1) Analogue signal wiring Stranded copper conductor, twisted pair or triad, flame retardant

with aluminum mylar tape or copper tape shield with drain wire, PVC insulated and PVC

overall jacketed type for analog signal wiring including RTD and frequency and digital

pulse signal(CVVS, CVV-I/C AMS type).

The cable shall be approved by vertical tray flame test.(KS C 3341, IEEE 383 or

equivalent) Twisted pair, triad, Multi-conductor cable : 1.5 mm2 (16 AWG) core size

2) Power supply and contact signal cables including those for solenoid valves shall be

stranded copper wire, binder tapes over core assembly, flame retardant with PVC

overall jacket type.

Core size shall be designed by the Vendor but not smaller than 2.5 mm2. (CVV type)

The cable shall be approved by vertical tray flame test.(KS C 3341, IEEE 383 or

equivalent)

5.2.5 Field mounted junction boxes (and/or terminal-blocks mounted in local control panel) shall

be provided in the packaged equipment in order to connect multi-conductor cable from/to

the control room. Terminal shall be provided for all cable cores and screens and including

minimum 20% spare.

5.3 Instrument Pressure Piping

5.3.1 1/2 inch pipes, socket weld valves and fittings as per the applicable piping specification

shall be used for the pressure gauge.

SK E&S Liquid Hydrogen DOC. NO. : SK-SP-IC-0001

Plug Power Refueling Station Project

REV. NO. : A

Specification for DATE : Oct. 29. 2021

Package Instrument

PAGE : 9 OF 9

5.4 Pneumatic Signal Tubing

316 stainless steel tube of 1/4 inch or 1/2 inch out-diameter x 0.049" thickness and 316

stainless steel compression fittings with double ferrules shall be used.

PAINTING

The manufacturer’s standard painting shall be applied for instruments.

NAME PLATES

Each instrument shall have a nameplate made of corrosion-resistance metal and all data shall

be clearly and deeply stamped into the metal by raised letters. The nameplate shall be

permanently attached to the instrument housing and bearing the following information.

1) Instrument tag number

2) Pressure Rating

3) Manufacturer's name and Model Number

4) Model number

5) Materials & Size (for control valves, PSV's and in-line flow elements)

6) Degree of Explosion Proof & Certificate Number

7) Calibrated Range (If appicable)

AA